Abstract

District 6 has had a lingering problem of low cylinder-strengths. This report describes, in detail, an ensuing investigation which incorporated the use of identical materials of concretes used in District 6 and analyses of cylinder data, in situ concrete cores, and laboratory mixtures. The investigation revealed that a high percent of the in situ concrete is sound and reliable, and that aggregate type and (or) air content were not the cause for the low cylinder-strengths. The quality of making, storing, and curing the cylinders were the reasons for low-strength.

Report Date

8-1-1977

Report Number

No. 477

Digital Object Identifier

http://dx.doi.org/10.13023/KTC.RR.1977.477

Notes

The contents of this report reflect the views of the author who is responsible for the facts and the accuracy of the data presented herein. The contents do not necessarily reflect the official views or policies of the Bureau of Highways. This report does not constitute a standard, specification, or regulation.